S1 (120Vac) and S2 (208-277Vac) High Performance 12 Watt/foot Roof Heater Cable Maximum Circuit Lengths In Feet
Model Number | Operating Voltage | Start-up Temp | Design Load (Amps/foot) @ 0° F. Startup |
Circuit Breaker Size | ||
---|---|---|---|---|---|---|
20A | 30A | 40A | ||||
S1 | 120 Vac | 20° F. | 135 | 175 | 175 | |
0° F. | 0.155 | 105 | 155 | 175 | ||
S2 | 208 Vac | 20° F. | 245 | 350 | 350 | |
0° F. | 0.083 | 190 | 290 | 350 | ||
S2 | 240 Vac | 20° F. | 250 | 350 | 350 | |
0° F. | 0.080 | 200 | 295 | 350 | ||
S2 | 277 Vac | 20° F. | 255 | 350 | 350 | |
0° F. | 0.077 | 205 | 310 | 350 | ||
Important: Ground fault protection is required for each circuit. Use only Summit Ice Melt Systems approved components for this type heating cable.